Energy management
Maximum number of devices,
maximum distances and absorptions
A system can manage up to 99 zone
addresses. Up to nine addresses
dedicated to the actuators can
be managed for each zone. The
maximum number of devices which
can be connected to the BUS also
depends on their total absorption
and the distance between the
connection point and the power
supply. The power supply can
supply up to 1200 mA (E46ADCN)
or 600 mA (E49) and the maximum
number of devices which can be
connected to the BUS is determined
by summing the absorption of all
the items and making sure that the
total does not exceed the capacity
of the power supply. For the
calculations mentioned above, refer
to the TECHNICAL DATA listed in the
Technical sheets section of this guide.
When calculating the absorptions the
availability of current as a function
of the length of the BUS cable must
also be considered. During the sizing
therefore respect the following rules:
the connection between the power
supply and the furthest device
must not be more than 250 m long;
MAXIMUM DISTANCES OF THE BUS CABLE
the total length of the connections
must not be more than 500m;
for best division of the currents
on the BUS line the power supply
should be installed in the middle.
With power supply E46ADCN:
A = 250 m max
B = 250 m max
A + B =500 m
Maximum current supplied
by the power supply: 1200 mA.
With power supply E49:
A = 250 m max
B = 250 m max
A + B =500 m
Maximum current supplied
by the power supply: 600 mA.
NOTE: If a UTP5 cable is used instead of a BUS L4669 cable, distances must halved.